€601.78 *
Net price €505.70 VAT: €96.08 *
Prices incl. VAT plus shipping costs
Delivery time 21 Workdays
- Order number: 95038399
- Manufacturer number: VT4025MSHNS000F
Type: VT4025MSHNS000F SIKA VTH 40 MS-410, SP-T1917 Pipe piece brass Turbine inner... more
Product information "Turbotron flow sensor SIKA VTH 40"
Type: VT4025MSHNS000F
SIKA VTH 40 MS-410, SP-T1917
Pipe piece brass
Turbine inner parts: PPO Noryl
G2 external thread
DN 40, PN 10
Pipe piece brass
Turbine inner parts: PPO Noryl
G2 external thread
DN 40, PN 10
Max. Medium temperature: 85°C
Measuring range: 6.7 to 417 l/min
Output: 26.6 pulses/liter, NPN open col
Hall sensor with integrated protective circuit
4-pin connector M12x1
The liquid flowing into the Turbotron turbine flow sensor is divided into partial jets by the guide blading. These hit the impeller evenly from different directions and set it in rotation. The speed of the impeller is now converted into an electrical pulse signal (frequency): the impeller is magnetically equipped, a Hall effect sensor detects the rotary movement. A flow-proportional frequency signal (square wave signal) is available. The geometry of the guide blades and impeller enables the very low start-up values to be achieved. Application areas: Monitoring of cooling circuits in machine and plant construction. water treatment. cleaning processes. dosage.
Measuring range: 6.7 to 417 l/min
Output: 26.6 pulses/liter, NPN open col
Hall sensor with integrated protective circuit
4-pin connector M12x1
The liquid flowing into the Turbotron turbine flow sensor is divided into partial jets by the guide blading. These hit the impeller evenly from different directions and set it in rotation. The speed of the impeller is now converted into an electrical pulse signal (frequency): the impeller is magnetically equipped, a Hall effect sensor detects the rotary movement. A flow-proportional frequency signal (square wave signal) is available. The geometry of the guide blades and impeller enables the very low start-up values to be achieved. Application areas: Monitoring of cooling circuits in machine and plant construction. water treatment. cleaning processes. dosage.
Output pulse/liter: | 26,6 Pulse / Liter |
Measuring range l/min: | 6,7 to 417 l/min |
Nominal size DN: | 40 |
Nominal pressure PN: | 10 |
Pipe piece: | With |
Connection material: | Brass |
Thread: | G2 |
Related links to "Turbotron flow sensor SIKA VTH 40"
Read, write and discuss reviews... more
Customer evaluation for "Turbotron flow sensor SIKA VTH 40"
Write an evaluation
Evaluations will be activated after verification.
Viewed